Refrigerant R452b

  • REFRIGERANT R452B

    Non-ozone depleting, low-GWP, HFO-based refrigerant to replace R410a in air conditioning, air-cooled and water-cooled chillers and heat pump applications

    Refrigerants

SUBSTITUTE FOR R410A IN THE NEW EQUIPMENT

R452b is a non-ozone depleting, low global warming potential, HFO-based refrigerant to replace R410a in positive displacement, direct expansion air conditioning, heat pump and chiller applications.

​R452b is intended for new equipment design only and is the preferred low-GWP replacement for R410a, as it offers the optimal balance of properties with an additional benefit of approximately 5% increase in energy efficiency while being easily convertible from R410a designs.

APPLICATIONS, PERFORMANCE, SAFETY AND ENVIRONMENTAL BENEFITS

R452b refrigerant

R452b helps deliver an optimal balance of performance, safety and design compatibility to replace R410a:

  • Improved performance: up to 5% energy efficiency improvement over R410a
  • Excellent performance in high ambient conditions
  • Mild flammability: ultra-low 2L class flammability properties
  • Equipment adaptability: close match to R410a with minimum changes required
  • Low GWP: 67% reduction in comparison to R410a
  • Very low temperature glide

R452B PROPERTIES

ASHRAE number

R452b

Composition

R32/R125/R1234yf

Boiling point @ 1atm [°C]

-51.0

Critical temperature [°C]

76.0

Ozone depletion potential

0

GWP AR5

675

ASHRAE safety class

A2L

Temperature glide [K]

1.0

Molecular weight [g/mol]

63.5

Liquid density @ 21.1°C [kg/m³]

1006.0

RELATED PRODUCTS

 

Lightstream Scroll II air-cooled chiller

Lightstream Scroll II

Multi-refrigerant air-cooled chillers with scroll compressor technology, combining efficient cooling and environment-safe operation for comfort and process cooling.
Discover more

Bora V-shaped evaporative condenser

Bora Condensers

Air-cooled condensers in V-shaped and horizontal designs, featuring microchannel heat exchangers and evaporative pre-cooling to boost energy efficiency.
Discover more

Low-charge air-cooled condenser

Borrum Condensers

Low-charge condensers featuring microchannel coils and EC fans. Engineered and optimized for use with low-GWP refrigerants in air conditioning and refrigeration applications.